Remote IO
SCI-RM44

SCI-RM44

Remote Control IO

• Programmable 4 x digital output and 4 x analog input
• I/O interface with industrial grade protection
• RS-485 industrial connectivity
• Wide operating temperature -20 ~ 70˚C
  • -20~70°C
DOWNLOAD
Specification
LED
LED 1 x for Power, 1 x for Serial port, 4 x for Digital Output
Power Supply
Power Requirement 12/24 VDC
Power Consumption 12V/2.29W, 24V/3.14W, normal used
Environmental and Mechanical
Dimension 160 x 106 x 27 mm (6.3” x 4.18” x 1.07”)
Weight < 0.45 kg
Mouting/Installation Din Rail
Operating Temperature -20 ~ 70 °C (-4 ~ 158 °F)
Storage Temperature -40 ~ 85 °C (-40 ~ 176 °F)
Operating Humidity 5% ~ 95% relative humidity, non-condensing
Certification
Regulations CE, FCC
Carrier Planning
Digital Output
Numbers of Channels 4
Output Types P-switching
Output Filter Output delay adjustable from 0 to 10s: No delay, 500 ms, 1s, 2s, 5s, 10s
Max output current 0.5 A
Switching frequency Ohmic load (min.47 RΩ): 1 kHz @24 VDC Inductive load: 0.2 Hz without free-wheeling diode, 1 kHZ with suitable free-wheeling diode, Lamp load (12 W): 1 kHz
Actuator connection 2-wire, with external DO power supply
DO external power supply Rated voltage: 24 VDC, Range: 9.6 ~ 31.2 VDC
Reverse polarity protection Yes
Short-circuit proof Yes
Individual channel diagnostic Yes
Safe Value Yes, Programmable
Analog Input
Connector Terminal Block
Number of Channels Max. 4 channels (Differential)
Voltage Input ±1 V, ±5 V, ±10 V ±100 mV, ±500 mV
Current Input ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA
TC Sensor Input J, K, T, E, R, S, B, N
RTD Sensor Types Platinum 100, α= 0.00385 (IEC), -200 ~ 600 °C/ Platinum 100, α= 0.00392 (JIS), -200 ~ 600°C/ Platinum 1000, α= 0.00385 (IEC), -200 ~ 600 °C
Resolution 16 bits
Sampling Rates 8 Hz
Accuracy ±0.1% of FSR
Disconnection Detection 4 ~ 20 mA, all T/C, all RTD
Channel Independent Configuration Yes
Input Impedance Voltage: > 100 KΩ, Current: 120 Ω
Serial Port
Connector Terminal Block (via x pins)
Ports/Channels 1
Serial Standards 4 W-RS-485, 2 W-RS-485 (software selectable)
RS-485 4 wire: Tx-, Tx+, Rx-, Rx+, 2 wire: Data-, Data+
Baud Rate 1,200 ~ 115,200 bps
Format (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1)
Pull High/Low Resistor for RS-485 1 kilo-ohm, 150 kilo-ohm
Terminator for RS-485 120 ohms
Protocol DCON, Modbus/RTU, Modbus/ASCII
Isolation 2 KV
Dimension